  "document": {
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited. (TLPv2: TLP:CLEAR)",
      "tlp": {
        "label": "WHITE"
      }
    },
    "lang": "en",
    "notes": [
      {
        "category": "summary",
        "text": "The web server in the CPCI85 firmware of SICAM A8000 CP-8031 and CP-8050 is affected by a path traversal vulnerability that could allow an authenticated remote attacker to traverse directories on the system, download arbitrary files and potentially escalate privileges to the administrator role.\n\nSiemens has released updates for the affected products and recommends to update to the latest versions.",
        "title": "Summary"
      },
      {
        "category": "general",
        "text": "Operators of critical power systems (e.g. TSOs or DSOs) worldwide are usually required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended that the operators check whether appropriate resilient protection measures are in place. The risk of cyber incidents impacting the grid's reliability can thus be minimized by virtue of the grid design.\nSiemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment. \nAs a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment.\n\nRecommended security guidelines can be found at:\n\nhttps://www.siemens.com/gridsecurity",
        "title": "General Recommendations"
      },
      {
        "category": "general",
        "text": "For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories",
        "title": "Additional Resources"
      },
      {
        "category": "legal_disclaimer",
        "text": "Siemens Security Advisories are subject to the terms and conditions contained in Siemens' underlying license terms or other applicable agreements previously agreed to with Siemens (hereinafter \"License Terms\"). To the extent applicable to information, software or documentation made available in or through a Siemens Security Advisory, the Terms of Use of Siemens' Global Website (https://www.siemens.com/terms_of_use, hereinafter \"Terms of Use\"), in particular Sections 8-10 of the Terms of Use, shall apply additionally. In case of conflicts, the License Terms shall prevail over the Terms of Use.",
        "title": "Terms of Use"
      }
    ],
    "publisher": {
      "category": "vendor",
      "contact_details": "productcert@siemens.com",
      "name": "Siemens ProductCERT",
      "namespace": "https://www.siemens.com"
    },
    "references": [
      {
        "category": "self",
        "summary": "SSA-770890: Path Traversal Vulnerability in the Web Server of CPCI85 Firmware of SICAM A8000 Devices - HTML Version",
        "url": "https://cert-portal.siemens.com/productcert/html/ssa-770890.html"
      },
      {
        "category": "self",
        "summary": "SSA-770890: Path Traversal Vulnerability in the Web Server of CPCI85 Firmware of SICAM A8000 Devices - CSAF Version",
        "url": "https://cert-portal.siemens.com/productcert/csaf/ssa-770890.json"
      },
      {
        "category": "self",
        "summary": "SSA-770890: Path Traversal Vulnerability in the Web Server of CPCI85 Firmware of SICAM A8000 Devices - PDF Version",
        "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-770890.pdf"
      },
      {
        "category": "self",
        "summary": "SSA-770890: Path Traversal Vulnerability in the Web Server of CPCI85 Firmware of SICAM A8000 Devices - TXT Version",
        "url": "https://cert-portal.siemens.com/productcert/txt/ssa-770890.txt"
      }
    ],
    "title": "SSA-770890: Path Traversal Vulnerability in the Web Server of CPCI85 Firmware of SICAM A8000 Devices",
    "tracking": {
      "current_release_date": "2023-10-10T00:00:00Z",
      "generator": {
        "engine": {
          "name": "Siemens ProductCERT CSAF Generator",
          "version": "1"
        }
      },
      "id": "SSA-770890",
      "initial_release_date": "2023-10-10T00:00:00Z",
      "revision_history": [
        {
          "date": "2023-10-10T00:00:00Z",
          "legacy_version": "1.0",
          "number": "1",
          "summary": "Publication Date"
        }
      ],
      "status": "interim",
      "version": "1"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "All versions < CPCI85 V05.11",
                "product": {
                  "name": "CP-8031 MASTER MODULE (6MF2803-1AA00)",
                  "product_id": "1",
                  "product_identification_helper": {
                    "model_numbers": [
                      "6MF2803-1AA00"
                    ]
                  }
                }
              }
            ],
            "category": "product_name",
            "name": "CP-8031 MASTER MODULE (6MF2803-1AA00)"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "All versions < CPCI85 V05.11",
                "product": {
                  "name": "CP-8050 MASTER MODULE (6MF2805-0AA00)",
                  "product_id": "2",
                  "product_identification_helper": {
                    "model_numbers": [
                      "6MF2805-0AA00"
                    ]
                  }
                }
              }
            ],
            "category": "product_name",
            "name": "CP-8050 MASTER MODULE (6MF2805-0AA00)"
          }
        ],
        "category": "vendor",
        "name": "Siemens"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2023-42796",
      "cwe": {
        "id": "CWE-22",
        "name": "Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal')"
      },
      "notes": [
        {
          "category": "summary",
          "text": "The web server of affected devices fails to properly sanitize user input for the /sicweb-ajax/tmproot/ endpoint.\r\n\r\nThis could allow an authenticated remote attacker to traverse directories on the system and download arbitrary files. By exploring active session IDs, the vulnerability could potentially be leveraged to escalate privileges to the administrator role.",
          "title": "Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "1",
          "2"
        ]
      },
      "remediations": [
        {
          "category": "mitigation",
          "details": "Restrict network access to the integrated web server",
          "product_ids": [
            "1",
            "2"
          ]
        },
        {
          "category": "mitigation",
          "details": "Review the list of users that are allowed to log in to the integrated web server and apply strong passwords",
          "product_ids": [
            "1",
            "2"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to CPCI85 V05.11 or later version",
          "product_ids": [
            "2"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109804985/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to CPCI85 V05.11 or later version",
          "product_ids": [
            "1"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109804985/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.1/AV:N/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C",
            "version": "3.1"
          },
          "products": [
            "1",
            "2"
          ]
        }
      ],
      "title": "CVE-2023-42796"
    }
  ]
}