  "document": {
    "title": "SSA-252466: Multiple Vulnerabilities in Climatix POL909 (AWM and AWB)",
    "category": "Siemens Security Advisory",
    "csaf_version": "2.0",
    "publisher": {
      "name": "Siemens ProductCERT",
      "contact_details": "productcert@siemens.com",
      "category": "vendor",
      "namespace": "https://www.siemens.com"
    },
    "distribution": {
      "text": "Disclosure is not limited.",
      "tlp": {
        "label": "WHITE"
      }
    },
    "tracking": {
      "id": "SSA-252466",
      "status": "final",
      "version": "1",
      "revision_history": [
        {
          "number": "1",
          "legacy_version": "1.0",
          "date": "2022-03-08T00:00:00Z",
          "summary": "Publication Date"
        }
      ],
      "initial_release_date": "2022-03-08T00:00:00Z",
      "current_release_date": "2022-03-08T00:00:00Z",
      "generator": {
        "engine": {
          "name": "Siemens ProductCERT CSAF Generator",
          "version": "1"
        }
      }
    },
    "notes": [
      {
        "title": "Summary",
        "category": "summary",
        "text": "Multiple vulnerabilities have been identified in the Climatix POL909 (AWM and AWB) that could allow an unauthenticated attacker to hijack and redirect users to a malicious webpage, or allow an authenticated attacker to access sensitive files.\n\nSiemens has released an update for the Climatix POL909 (AWM and AWB) and recommends to update to the latest version."
      },
      {
        "title": "General Recommendations",
        "category": "general",
        "text": "As a general security measure Siemens strongly recommends to protect network access to affected products with appropriate mechanisms. It is advised to follow recommended security practices in order to run the devices in a protected IT environment."
      },
      {
        "title": "Additional Resources",
        "category": "general",
        "text": "For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories"
      },
      {
        "title": "Terms of Use",
        "category": "legal_disclaimer",
        "text": "Siemens Security Advisories are subject to the terms and conditions contained in Siemens' underlying license terms or other applicable agreements previously agreed to with Siemens (hereinafter \"License Terms\"). To the extent applicable to information, software or documentation made available in or through a Siemens Security Advisory, the Terms of Use of Siemens' Global Website (https://www.siemens.com/terms_of_use, hereinafter \"Terms of Use\"), in particular Sections 8-10 of the Terms of Use, shall apply additionally. In case of conflicts, the License Terms shall prevail over the Terms of Use."
      }
    ],
    "references": [
      {
        "category": "self",
        "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-252466.pdf",
        "summary": "SSA-252466: Multiple Vulnerabilities in Climatix POL909 (AWM and AWB) - PDF Version"
      },
      {
        "category": "self",
        "url": "https://cert-portal.siemens.com/productcert/txt/ssa-252466.txt",
        "summary": "SSA-252466: Multiple Vulnerabilities in Climatix POL909 (AWM and AWB) - TXT Version"
      },
      {
        "category": "self",
        "url": "https://cert-portal.siemens.com/productcert/csaf/ssa-252466.json",
        "summary": "SSA-252466: Multiple Vulnerabilities in Climatix POL909 (AWM and AWB) - CSAF Version"
      }
    ]
  },
  "product_tree": {
    "branches": [
      {
        "name": "Siemens",
        "category": "vendor",
        "branches": [
          {
            "name": "Climatix POL909 (AWB module)",
            "category": "product_name",
            "branches": [
              {
                "name": "< V11.44",
                "category": "product_version_range",
                "product": {
                  "product_id": "1",
                  "name": "Climatix POL909 (AWB module)"
                }
              }
            ]
          },
          {
            "name": "Climatix POL909 (AWM module)",
            "category": "product_name",
            "branches": [
              {
                "name": "< V11.36",
                "category": "product_version_range",
                "product": {
                  "product_id": "2",
                  "name": "Climatix POL909 (AWM module)"
                }
              }
            ]
          }
        ]
      }
    ]
  },
  "vulnerabilities": [
    {
      "title": "CVE-2021-41541",
      "notes": [
        {
          "title": "Summary",
          "category": "summary",
          "text": "The Group Management page of affected devices is vulnerable to cross-site scripting (XSS). The vulnerability allows an attacker to send malicious JavaScript code which could result in hijacking of the user's cookie/session tokens, redirecting the user to a malicious webpage and performing unintended browser action."
        }
      ],
      "cve": "CVE-2021-41541",
      "cwe": {
        "id": "CWE-79",
        "name": "Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting')"
      },
      "product_status": {
        "known_affected": [
          "1",
          "2"
        ]
      },
      "scores": [
        {
          "cvss_v3": {
            "version": "3.1",
            "baseScore": 6.5,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:N/E:P/RL:O/RC:C"
          },
          "products": [
            "1",
            "2"
          ]
        }
      ],
      "remediations": [
        {
          "product_ids": [
            "1"
          ],
          "category": "vendor_fix",
          "details": "Update to V11.44 or later version",
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109747351/"
        },
        {
          "product_ids": [
            "2"
          ],
          "category": "vendor_fix",
          "details": "Update to V11.36 or later version",
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109747351/"
        }
      ],
      "references": [
        {
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109747351/",
          "summary": "CVE-2021-41541 - Climatix POL909 (AWB module)"
        },
        {
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109747351/",
          "summary": "CVE-2021-41541 - Climatix POL909 (AWM module)"
        },
        {
          "url": "https://cert-portal.siemens.com/productcert/mitre/CVE-2021-41541.json",
          "summary": "CVE-2021-41541 Mitre 5.0 json"
        }
      ]
    },
    {
      "title": "CVE-2021-41542",
      "notes": [
        {
          "title": "Summary",
          "category": "summary",
          "text": "The User Management page of affected devices is vulnerable to cross-site scripting (XSS). The vulnerability allows an attacker to send malicious JavaScript code which could result in hijacking of the user's cookie/session tokens, redirecting the user to a malicious webpage and performing unintended browser action."
        }
      ],
      "cve": "CVE-2021-41542",
      "cwe": {
        "id": "CWE-79",
        "name": "Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting')"
      },
      "product_status": {
        "known_affected": [
          "1",
          "2"
        ]
      },
      "scores": [
        {
          "cvss_v3": {
            "version": "3.1",
            "baseScore": 6.5,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:N/E:P/RL:O/RC:C"
          },
          "products": [
            "1",
            "2"
          ]
        }
      ],
      "remediations": [
        {
          "product_ids": [
            "1"
          ],
          "category": "vendor_fix",
          "details": "Update to V11.44 or later version",
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109747351/"
        },
        {
          "product_ids": [
            "2"
          ],
          "category": "vendor_fix",
          "details": "Update to V11.36 or later version",
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109747351/"
        }
      ],
      "references": [
        {
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109747351/",
          "summary": "CVE-2021-41542 - Climatix POL909 (AWB module)"
        },
        {
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109747351/",
          "summary": "CVE-2021-41542 - Climatix POL909 (AWM module)"
        },
        {
          "url": "https://cert-portal.siemens.com/productcert/mitre/CVE-2021-41542.json",
          "summary": "CVE-2021-41542 Mitre 5.0 json"
        }
      ]
    },
    {
      "title": "CVE-2021-41543",
      "notes": [
        {
          "title": "Summary",
          "category": "summary",
          "text": "The handling of log files in the web application of affected devices contains an information disclosure vulnerability which could allow logged in users to access sensitive files."
        }
      ],
      "cve": "CVE-2021-41543",
      "cwe": {
        "id": "CWE-284",
        "name": "Improper Access Control"
      },
      "product_status": {
        "known_affected": [
          "1",
          "2"
        ]
      },
      "scores": [
        {
          "cvss_v3": {
            "version": "3.1",
            "baseScore": 4.3,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:L/I:N/A:N/E:P/RL:O/RC:C"
          },
          "products": [
            "1",
            "2"
          ]
        }
      ],
      "remediations": [
        {
          "product_ids": [
            "1"
          ],
          "category": "vendor_fix",
          "details": "Update to V11.44 or later version",
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109747351/"
        },
        {
          "product_ids": [
            "2"
          ],
          "category": "vendor_fix",
          "details": "Update to V11.36 or later version",
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109747351/"
        }
      ],
      "references": [
        {
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109747351/",
          "summary": "CVE-2021-41543 - Climatix POL909 (AWB module)"
        },
        {
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109747351/",
          "summary": "CVE-2021-41543 - Climatix POL909 (AWM module)"
        },
        {
          "url": "https://cert-portal.siemens.com/productcert/mitre/CVE-2021-41543.json",
          "summary": "CVE-2021-41543 Mitre 5.0 json"
        }
      ]
    }
  ]
}